Eco GC

Auto Start Load Share unit

Multi genset load sharing (up to 32 gensets)
kW and kV Ar load sharing
Busbar voltages and frequency measurements
Dead bus sensing
Bus failure detection
Sequential set start
Manual voltage/frequency adjustment
Load dependent automatic Start/Stop
Equal aging of gensets
Direct/Reverse governor and AVR control
Volts,frequency and phase matching
Synchroscope display
Logic Controller functionality for PLC
Black or gray theme selection for 4.3″ TFT LCD screen

  • Pre-Alarm                                Engine temperature
    Oil pressure
    Fuel level
    Over / Under voltage
    Over / Under frequency
    Over / Under speed
  • Warning & Electrical trip
    Earth fault
    Over current
    Short circuit
  • Alarm
    Generator breaker not opened
    Generator breaker not closed
  • Controls
    Fuel and Stop solenoid
    ECU power and stop
    Starter motor
    Automatic generator start
    Preheat
    External alarm horn
    Engine cooling
    Idle mode
  •   Fail Monitoring    Emergency stop
    Failed to start
    Low oil pressure
    High temperature
    Speed failure
    Voltage failure
    Charging fail
    Shutdown
    Warning
  • Error

    Over / Under speed
    Speed loss
    Earth fault
    Fuel level
    Battery low
    Battery high
    Maintenance
    Over current
    Short circuit
    Engine stop
    CanBus
    Charge alternator

Dimensions

Panel Cut-Out

Protection 

Weight

Environmental Rating 

Operating/Storage Temperature 

Operating/Storage Humidity

DC Battery Supply Voltage 

CT Secondary 

Sender Measurement 

Communication Interface 

: 276 mm x 189 mm x 45 mm. (including connectors). Plastic housing for panel mounting.

: Panel Cut-Out : 223mm x 162mm.

: IP65 at front panel.

: Approximately 0,82 Kg.

: Standard, indoor at an altitude of less then 2000 meters with non-condensing humidity.

: -20°C to +70°C / -30°C to +80°C

: 95% max. (non-condensing)

: 8 to 32 V dc (Peak: 36Vdc) Max. operating current is 860 mA.

: 5A.

: 0 to 1300 ohm, accuracy: 1 % FS, resolution: 1 ohm.

: USB programming and communication port, CanBus
communication with 1939 ECU, CanOpen, Ethernet, RS485.